Automatic Extinguishing System
Submittal Requirements
Fully dimensioned plans to scale
Calculation sheets as appropriate
Agent being used and the amount provided
Manufacturer’s Data sheets shall be provided for all equipment
Description of occupancies and/or hazards being protected, designating whether or not the enclosure is normally occupied
Description of exposures surrounding the enclosure or protected area
Description of agent storage containers used to include internal volume, storage pressure, and nominal capacity expressed in units of agent mass or volume at standard conditions of temperature and pressure
Description of nozzles used to include size, orifice port, configuration and equivalent orifice area and material
Description of pipe and fittings used to include material specifications, grade and pressure rating
Plan view of the protected area showing enclosure partitions; agent distribution system including agent storage containers, piping and nozzles, location of controlled devices such as dampers and shutters and location of instructional signage, location of manual pull station, location of notification devices
Location and function of the detection device(s)
Length of time delay for pre-discharge alarm (if applicable)
Location and description of warning signs (if applicable)
Details of container securement
Details of any special features
Required Inspections
Rough-in (Exposed piping)
System activation
Room integrity test (If applicable)
Signal verification to central monitoring
Questions
If you have any additional questions, email rogersfd@rogersmn.gov or call 763-428-3500.