Gas Detection Systems
Image of a gas detection system with a rectangular box, switches, and colorful lights that indicate gas levels, ensuring safety in environments at risk for gas leaks.
Plan Submittal Requirements
Floor plans showing the location of the gas detection system in the building that is fully dimensioned and to scale
All details on system components and building construction features shall be clearly legible.
Identify the type of gas detection system or equipment being installed or modified:
Type of gas being detected
Gas alarm threshold limits
Sensor locations
Alarm notification appliances
Submit Safety Data Sheets (SDS) for all gases being detected.
Plans on any interlock systems (safety features) as required.
Adequate, concise, and sufficient information as required by MSFC and NFPA shall be clearly indicated on the plans.
Manufacturer’s data sheets shall be provided for all equipment.
Designers name, business name, contact information, and proof of licensure (if required).
Questions
If you have any additional questions, email rogersfd@rogersmn.gov or call 763-428-3500.